Project intrinsic safety verification

Maintain multiple independent single-source IS instrument loops and generate one consolidated client-facing screening report. No internet connection required.

● Project-level calculator v2.0

Project / document details

Shown once on the client report

Uses a FluiMix-style text mark until you upload your official logo. Included in exported JSON.

Project instrument register

Select a loop to edit its IS entity values

0 loops
TagInstrument / interfaceScreening
Engineering limitation: This application only performs preliminary entity-parameter screening for one independent power source and one field device per loop. Multi-source circuits, FISCO, special control drawings, cable fault analysis, EPL, gas/temperature suitability, installation and all certificate conditions require separate assessment.

Instrument details

Fields are specific to the selected IS loop

INCOMPLETE
Associated apparatus · isolator / barrier output
Field apparatus · certified input limits
Cable · interconnection parameters
Engineering document review

Live entity-parameter screening

Displayed ratios: calculated total / entered certified limit

Select an instrumentINCOMPLETE

Consolidated client report

One line per instrument, with traceable entity values and an overall project screening result.

F
FluiMix
ENGINEERING SERVICES

INTRINSIC SAFETY — LOOP VERIFICATION REGISTER

Consolidated entity-parameter screening · One source / one field instrument per loop

Project—
Client—
Project No.—
Document No.—
Revision—
Date—
PROJECT SCREENING — INCOMPLETE
Loops 0Numeric pass + reviewed 0Fail 0Review 0Incomplete 0
No.Instrument tag / modelIS isolator / modelGroupUo / Ui
(V)
Io / Ii
(mA)
Po / Pi
(mW)
ΣC / Co*
(nF)
ΣL / Lo*
(mH)
Result

Calculation basis and limitations

Uo ≤ Ui; Io ≤ Ii; Po ≤ Pi; ΣC = Ci + (cable length × pF/m ÷ 1,000) ≤ Co*; ΣL = Li ÷ 1,000 + (cable length × µH/m ÷ 1,000) ≤ Lo*. Co* and Lo* are adjusted limits where the applicable linear-source mixed-reactance 50% rule is triggered.

Numerical results only: use actual certification / control drawings and selected gas group. This table alone does not establish installation compliance, Ex protection suitability or a full IEC 60079-25 descriptive system document.

Report notes

—

Legend: NUM PASS = all five checks pass and three review declarations completed; REVIEW = numerical pass with outstanding verification or special evaluation; FAIL = at least one numerical limit exceeded; INCOMPLETE = missing or invalid data.

Prepared by—
Checked / approved by—
Document classificationPreliminary engineering screening — approval required
FluiMix · Project-level IS loop screening register—Page 1 of 1 (within selected loop capacity)