Project / document details
Shown once on the client report
Maintain multiple independent single-source IS instrument loops and generate one consolidated client-facing screening report. No internet connection required.
Shown once on the client report
Select a loop to edit its IS entity values
Fields are specific to the selected IS loop
Displayed ratios: calculated total / entered certified limit
One line per instrument, with traceable entity values and an overall project screening result.
Consolidated entity-parameter screening · One source / one field instrument per loop
| No. | Instrument tag / model | IS isolator / model | Group | Uo / Ui (V) | Io / Ii (mA) | Po / Pi (mW) | ΣC / Co* (nF) | ΣL / Lo* (mH) | Result |
|---|
Uo ≤ Ui; Io ≤ Ii; Po ≤ Pi; ΣC = Ci + (cable length × pF/m ÷ 1,000) ≤ Co*; ΣL = Li ÷ 1,000 + (cable length × µH/m ÷ 1,000) ≤ Lo*. Co* and Lo* are adjusted limits where the applicable linear-source mixed-reactance 50% rule is triggered.
Numerical results only: use actual certification / control drawings and selected gas group. This table alone does not establish installation compliance, Ex protection suitability or a full IEC 60079-25 descriptive system document.
—
Legend: NUM PASS = all five checks pass and three review declarations completed; REVIEW = numerical pass with outstanding verification or special evaluation; FAIL = at least one numerical limit exceeded; INCOMPLETE = missing or invalid data.